Name/function
Ext DC Fault Reporting
Ext DC Fault Delay
(minutes)
Explanation (checkbox)
Enabled
Reports that a fault has occurred with the external DC power supply.
Deactivated
Function not possible.
Delay time in minutes (0–60 minutes) until the message is sent.
If a DC Fault occurs the alarm panel displays an error message after a few sec-
onds, "General Fault" outputs activate and a log book entry is created (Mandatory
Events).
Power disruptions that last less than 9 s are not reported.
If the power supply is restored within these 9 seconds, the "General Fault" outputs
are reset and a log book entry is created: "Power supply restored".
If the power disruption lasts longer than 9 s, the following occurs:
 If the value is set to 0 min, a warning tone is sounded after 10 s and the alarm
panel reports the failure. "DC Fault" outputs are activated.
 If the value is set to higher than 0 min, this timer is started 10 s after the disruption
occurs.
If the power supply is restored before the end of the set delay time, "General Fault"
outputs are reset and a log book entry is created about the power restore.
No errors are reported.
If the fault still exists after the end of the configured time, a warning tone sounds
and the error is reported. "DC Fault" outputs are activated.
A user can stop the warning tone by entering their code. The alarm panel display
shows details of the warning. "General Fault" and "DC Fault" outputs remain acti-
vated.
If the fault has been corrected, the alarm panel deactivates the "DC Fault" outputs
and creates a log book entry about the power restore. A user can reset the alarm
and the "General Fault" outputs after entering their user code.
Configuration
119