How to Install

4.2.2 Receiving the Frequency Converter

When receiving the frequency converter, make sure that
the packaging is intact, and be aware of any damage that
might have occurred to the unit during transport. In case
damage has occurred, contact immediately the shipping
company to claim the damage.

4.2.3 Transportation and Unpacking

Before unpacking the frequency converter it is
recommended that it is located as close as possible to the
final installation site.
Remove the box and handle the frequency converter on
the pallet, as long as possible.

4.2.4 Lifting

Always lift the frequency converter in the dedicated lifting
eyes. For all D and E frames, use a bar to avoid bending
the lifting holes of the frequency converter.
Illustration 4.2 Recommended lifting method, frame size D 13
Illustration 4.3 Recommended lifting method, frame size E 9
WARNING
The lifting bar must be able to handle the weight of the
frequency converter. See 4.2.5 Mechanical Dimensions for
the weight of the different frame sizes. Maximum diameter
for bar is 2.5 cm (1 inch). The angle from the top of the
frequency converter to the lifting cable should be 60° or
greater.
VLT AQUA Low Harmonic Drive Operating Instructions
Lifting Holes
Lifting Holes
Illustration 4.4 Recommended lifting method, frame size F18 -
filter section.
®