VLT AQUA Low Harmonic Drive Operating Instructions
6.2.1 Using the Low Harmonic Drive in NPN
Mode
The default setting for 5-00 Digital I/O Mode is PNP mode.
If NPN mode is desired, it is necessary to change the
wiring in the filter part of the Low Harmonic Drive. Before
changing the setting in 5-00 Digital I/O Mode to NPN
mode, the wire connected to 24 V (control terminal 12 or
13) must be changed to terminal 20 (ground).