How to Install

4.6.12 External Fan Supply

In case the frequency converter is supplied by DC or if the
fan must run independently of the power supply, an
external power supply can be applied. The connection is
made on the power card.
Terminal No.
Function
100, 101
Auxiliary supply S, T
102, 103
Internal supply S, T
The connector located on the power card provides the
connection of line voltage for the cooling fans. The fans
are connected from factory to be supplied form a common
AC line (jumpers between 100-102 and 101-103). If external
supply is needed, the jumpers are removed and the supply
is connected to terminals 100 and 101. A 5 Amp fuse
should be used for protection. In UL applications this
should be LittleFuse KLK-5 or equivalent.
4.6.13 Power and Control Wiring for
Unscreened Cables
WARNING
Induced Voltage!
Run motor cables from multiple drives separately. Induced
voltage from output motor cables run together can charge
equipment capacitors even with the equipment turned off
and locked out. Failure to run output cables separately
could result in death or serious injury.
WARNING
Run drive input power, motor wiring, and control wiring in
three separate metallic conduits or raceways for high
frequency noise isolation. Failure to isolate power, motor,
and control wiring could result in less than optimum
controller and associated equipment performance.
Because the power wiring carries high frequency electrical
pulses, it is important that input power and motor power
are run in separate conduit. If the incoming power wiring
is run in the same conduit as the motor wiring, these
pulses can couple electrical noise back onto the building
power grid. Control wiring should always be isolated from
the high voltage power wiring.
When screened/armoured cable is not used, at least three
separate conduits must be connected to the panel option.
VLT AQUA Low Harmonic Drive Operating Instructions

4.6.14 Fuses

It is recommended to use fuses and/ or circuit breakers on
the supply side as protection in case of component break-
down inside the frequency converter (first fault).
NOTE
This is mandatory in order to ensure compliance with IEC
60364 for CE or NEC 2009 for UL.
Personnel and property must be protected against the
consequence of component break-down internally in the
frequency converter.
Branch Circuit Protection
In order to protect the installation against electrical and
fire hazard, all branch circuits in an installation, switch
gear, machines etc., must be protected against short-circuit
and over-current according to national/international
regulations.
NOTE
The recommendations given do not cover Branch circuit
protection for UL.
Short-circuit protection:
Danfoss recommends using the fuses/Circuit Breakers
mentioned below to protect service personnel and
property in case of component break-down in the
frequency converter.
Non UL compliance
If UL/cUL is not to be complied with, we recommend using
the following fuses, which will ensure compliance with
EN50178:
P160 - P250
P315 - P450
UL Compliance
380-480 V, frame sizes D, E and F
The fuses below are suitable for use on a circuit capable of
delivering 100,000 Arms (symmetrical), 240 V, or 480 V, or
500 V, or 600 V depending on the frequency converter
voltage rating. With the proper fusing the frequency
converter Short Circuit Current Rating (SCCR) is 100,000
Arms.
®
MG20T202 - VLT
is a registered Danfoss trademark
Power wiring into the enclosure
Power wiring from the enclosure to the motor
Control wiring
WARNING
380 - 480 V
380 - 480 V
4
4
type gG
type gR
47