Troubleshooting
Bit
Hex
17
00020000
18
00040000
19
00080000
20
00100000
21
00200000
22
00400000
23
00800000
24
01000000
9
9
25
02000000
26
04000000
27
08000000
28
10000000
29
20000000
30
40000000
31
80000000
Table 9.2 Description of Alarm Word, Warning Word and Extended Status Word
The alarm words, warning words and extended status words can be read out via serial bus or optional fieldbus for diagnose.
See also 16-94 Ext. Status Word.
158
VLT AQUA Low Harmonic Drive Operating Instructions
Dec
Alarm Word
131072
Internal Fault (A38) KTY error
262144
Brake Overload
(A26)
524288
U phase Loss (A30) ECB error
1048576
V phase Loss (A31) reserved
2097152
W phase Loss (A32) reserved
4194304
Fieldbus Fault (A34) reserved
8388608
24 V Supply Low
(A47)
16777216
Mains Failure (A36) reserved
33554432
1.8V Supply Low
(A48)
67108864
Brake Resistor (A25) reserved
134217728
Brake IGBT (A27)
268435456
Option Change
(A67)
536870912
Drive
Initialized(A80)
1073741824 Safe Stop (A68)
2147483648 Mech. brake low
(A63)
MG20T202 - VLT
Alarm Word 2
Warning Word
10V Low (W1)
Fans error
Brake Overload (W26)
Brake Resistor (W25)
Brake IGBT (W27)
Speed Limit (W49)
Fieldbus Fault (W34)
reserved
24V Supply Low (W47)
Mains Failure (W36)
reserved
Current Limit (W59)
Low Temp (W66)
reserved
Voltage Limit (W64)
reserved
Encoder loss (W90)
Feedback Fault
Feedback Fault (W61,
(A61, A90)
W90)
PTC 1 Safe Stop
Safe Stop (W68)
(A71)
Dangerous Failure
Extended Status Word
(A72)
®
is a registered Danfoss trademark
Warning
Extended
Word 2
Status Word
KTY Warn
Password Timelock
number of allowed
password trials
exceeded - timelock
active
Fans Warn
Password Protection
0-61 =
ALL_NO_ACCESS OR
BUS_NO_ACCESS OR
BUS_READONLY
ECB Warn
Reference High
reference > 4-55
reserved
Reference Low
reference < 4-54
reserved
Local Reference
reference site =
REMOTE -> auto on
pressed & active
reserved
Protection Mode
reserved
Unused
reserved
Unused
reserved
Unused
reserved
Unused
reserved
Unused
reserved
Unused
Unused
PTC 1 Safe
Unused
Stop (W71)
Unused