22-31 Power Correction Factor
Range:
Function:
100 %
[1 - 400
Make corrections to the calculated power at
*
%]
22-30 No-Flow Power.
If No Flow is detected, when it should not be
detected, the setting should be decreased.
However, if No Flow is not detected, when it
should be detected, the setting should be
increased to above 100%.
22-32 Low Speed [RPM]
Range:
Function:
Size
[
0 - par.
To be used if 0-02 Motor Speed Unit
related
22-36 RPM]
has been set for RPM (parameter not
*
visible if Hz selected).
Set used speed for the 50% level.
This function is used for storing values
needed to tune No Flow Detection.
22-33 Low Speed [Hz]
Range:
Function:
Size
[ 0.0 - par.
To be used if 0-02 Motor Speed Unit
related
22-37 Hz]
has been set for Hz (parameter not
*
visible if RPM selected).
Set used speed for the 50% level.
The function is used for storing values
needed to tune No Flow Detection.
22-34 Low Speed Power [kW]
Range:
Function:
Size
[
0.00 -
To be used if 0-03 Regional Settings has
related
0.00 kW]
been set for International (parameter
*
not visible if North America selected).
Set power consumption at 50% speed
level.
This function is used for storing values
needed to tune No Flow Detection.
22-35 Low Speed Power [HP]
Range:
Function:
Size
[
0.00 -
To be used if 0-03 Regional Settings has
related
0.00 hp]
been set for North America (parameter
*
not visible if International selected).
Set power consumption at 50% speed
level.
This function is used for storing values
needed to tune No Flow Detection.
22-36 High Speed [RPM]
Range:
Function:
Size
[
0 - par.
To be used if 0-02 Motor Speed Unit
related
4-13 RPM]
has been set for RPM (parameter not
*
visible if Hz selected).
Set used speed for the 85% level.
VLT AQUA Low Harmonic Drive Operating Instructions
22-36 High Speed [RPM]
Range:
22-37 High Speed [Hz]
Range:
Size
related
22-38 High Speed Power [kW]
Range:
Size
related
22-39 High Speed Power [HP]
Range:
Size
related
22-40 Minimum Run Time
Range:
10 s
22-41 Minimum Sleep Time
Range:
10 s
®
MG20T202 - VLT
is a registered Danfoss trademark
Function:
The function is used for storing values
needed to tune No Flow Detection.
Function:
[
0.0 -
To be used if 0-02 Motor Speed Unit has
par. 4-14
been set for Hz (parameter not visible
*
Hz]
if RPM selected).
Set used speed for the 85% level.
The function is used for storing values
needed to tune No Flow Detection.
Function:
[
0.00 -
To be used if 0-03 Regional Settings has
0.00 kW]
been set for International (parameter
*
not visible if North America selected).
Set power consumption at 85% speed
level.
This function is used for storing values
needed to tune No Flow Detection.
Function:
[
0.00 -
To be used if 0-03 Regional Settings has
0.00 hp]
been set for North America (parameter
*
not visible if International selected).
Set power consumption at 85% speed
level.
This function is used for storing values
needed to tune No Flow Detection.
Function:
[0 - 600 s] Set the desired minimum running time for
*
the motor after a start command (digital
input or Bus) before entering Sleep Mode.
Function:
[0 - 600 s] Set the desired Minimum Time for staying in
*
Sleep Mode. This will override any wake up
conditions.
6
6
93