Danfoss VLT AQUA Drive FC 200 Operating Instructions Manual page 86

Low harmonic drive
Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

How to Programme the Low Ha...
[120]
Lead Pump
Starts/Stops the Lead Pump (controlled by
Start
the frequency converter). A start requires
that also a System Start signal has been
applied e.g. to one of the digital inputs set
for [8] Start!
[121]
Lead Pump
Forces alternation of the lead pump in a
Alternation
Cascade Controller. Lead Pump Alternation,
25-50 Lead Pump Alternation must be set to
either [2] At Command or [3] At Staging or At
Command. Alternation Event,
25-51 Alternation Event can be set to any of
the four options.
[130
Pump1
The function will depend on the setting in
-
Interlock -
25-06 Number of Pumps. If set to [0] No,
138]
Pump9
then Pump1 refers to the pump controlled
Interlock
by relay RELAY1 etc. If set to [1] Yes, Pump1
refers to the pump controlled by the
frequency converter only (without any of
the build in relays involved) and Pump2 to
the pump controlled by the relay RELAY1.
Variable speed pump (lead) cannot be
interlocked in the basic Cascade Controller.
See Table 6.4
Setting in
parameter
group 5-1*
[130] Pump1
Interlock
[131] Pump2
Interlock
[132] Pump3
Interlock
[133] Pump4
Interlock
[134] Pump5
Interlock
[135] Pump6
Interlock
[136] Pump7
Interlock
[137] Pump8
Interlock
[138] Pump9
Interlock
5-13 Terminal 29 Digital Input
Option:
Function:
[0]
No Operation Same options and functions as parameter
*
group 5-1* Digital Inputs.
VLT AQUA Low Harmonic Drive Operating Instructions
Setting in 25-06 Number of
Pumps
[0] No
[1] Yes
Controlled
Frequency
by RELAY1
Converter
(only if not
controlled
lead pump)
(cannot be
interlocked)
Controlled
Controlled by
by RELAY2
RELAY1
Controlled
Controlled by
by RELAY3
RELAY2
Controlled
Controlled by
by RELAY4
RELAY3
Controlled
Controlled by
by RELAY5
RELAY4
Controlled
Controlled by
by RELAY6
RELAY5
Controlled
Controlled by
by RELAY7
RELAY6
Controlled
Controlled by
by RELAY8
RELAY7
Controlled
Controlled by
by RELAY9
RELAY8
®
MG20T202 - VLT
is a registered Danfoss trademark
5-14 Terminal 32 Digital Input
Option:
Function:
[0]
No Operation Same options and functions as parameter
*
group 5-1* Digital Inputs, except for Pulse
input.
5-15 Terminal 33 Digital Input
Option:
Function:
[0]
No Operation Same options and functions as parameter
*
group 5-1* Digital Inputs.
5-30 Terminal 27 Digital Output
Same options and functions as parameter group 5-3*.
Option:
[0]
No operation
*
5-40 Function Relay
Option:
Function:
Select options to define the
function of the relays.
The selection of each mechanical
relay is realized in an array
parameter.
[0]
No operation
*
[1]
Control ready
[2]
Drive ready
[3]
Drive rdy/rem ctrl
[4]
Enable / no warning
[5]
Running
[6]
Running / no warning
[7]
Run in range/no warn
[8]
Run on ref/no warn
[9]
Alarm
[10]
Alarm or warning
[11]
At torque limit
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[15]
Out of speed range
[16]
Below speed, low
[17]
Above speed, high
[18]
Out of feedb. range
[19]
Below feedback, low
[20]
Above feedback, high
[21]
Thermal warning
[22]
Ready,no thermal W
[23]
Remote,ready,no TW
[24]
Ready, Voltage OK
[25]
Reverse
[26]
Bus OK
[27]
Torque limit & stop
[28]
Brake, no brake war
[29]
Brake ready, no fault
[30]
Brake fault (IGBT)
Function:
6
85
6

Advertisement

Table of Contents