Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
5.4.2

Starting quick commissioning

Requirement
The following requirements apply:
• The power supply is switched on.
• The operator panel displays setpoints and actual values.
Function description
Procedure
Press the ESC key.
Press one of the arrow keys until the BOP-2 displays menu
To start quick commissioning, press the OK key in menu
We recommend resetting the converter to the factory setting before commencing quick
commissioning.
Should you wish to change the default setting of the interfaces, the converter must be reset
to the factory settings now.
Proceed as follows:
1. Press the OK key.
2. Switch over the display using an arrow key:
3. Press the OK key.
5.4.3

Select the application class

Overview
When selecting an application class, the converter assigns the appropriate settings to the motor
control.
If you do not set the application class, but instead setting "Expert", then you must define the
appropriate closed-loop motor control setting.
126
Select the application class (Page 126)
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
.
.
SINAMICS G120C Converters