Set Up Cybersentry And Change Default Password - GE C70 Instruction Manual

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

CHAPTER 3: INSTALLATION
2.
Select the Ethernet interface and enter the IP address assigned to the C70, then click the Connect button. The
EnerVista UR Setup software creates a site named "Quick Connect" with a corresponding device also named "Quick
Connect" and displays them in the Online Window.
3.
Expand the sections to view data directly from the C70 device. Use the Device Setup button to change the site name.
Each time that the EnerVista software is initialized, click the Quick Connect button to establish direct communications to
the C70. This ensures that configuration of the EnerVista UR Setup software matches the C70 model number.

3.9 Set up CyberSentry and change default password

If and when first using CyberSentry security, use the following procedure for set up.
1.
Log in to the relay as Administrator by using the
(so that no IP address is required). If logging in through EnerVista choose Device authentication (see figure). Enter the
default password "ChangeMe1#". Note that the "Lock relay" setting needs to be disabled in the Security > Supervisory
menu. When this setting is disabled, configuration and firmware upgrade are possible. By default, this setting is
disabled.
2.
Enable the Supervisor role if you have a need for it.
3.
Make any required changes in configuration, such as setting a valid IP address for communication over Ethernet.
4.
Log out of the Administrator account by choosing None.
Next, device or server authentication can be chosen on the login screen, but the choice is available only in EnerVista. Use
Device authentication to log in using the five pre-configured roles (Administrator, Supervisor, Engineer, Operator, Observer,
or Administrator and Supervisor when Device authentication is disabled). When using a serial connection, only Device
authentication is supported. When Server authentication is required, characteristics for communication with a RADIUS
server must be configured on the UR. This is possible only through the EnerVista software. The RADIUS server itself also
must be configured. At the end of this instruction manual, the appendix called RADIUS Server Configuration gives an
example of how to set up a simple RADIUS server. Once both the RADIUS server and the parameters for connecting the UR
to the server have been configured, you can choose Server authentication on the login screen of EnerVista.
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Figure 3-64: Quick Connect window for Ethernet connection
keys on the front panel or through EnerVista connected serially
VALUE
SET UP CYBERSENTRY AND CHANGE DEFAULT PASSWORD
3
3-65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents