2.5.2
Tell controller status.vi
This VI returns the controller's state and the controller's error.
The controller's error is composed of 4 digits (abcd) coded in hexadecimal, each bit of
the error byte is described below:
Digit d bit 0: negative end of run.
Digit d bit 1: positive end of run.
Digit d bit 2: peak current limit.
Digit d bit 3: rms current limit.
Digit c bit 0: short circuit detection.
Digit c bit 1: following error.
Digit c bit 2: time out homing.
Digit c bit 3: bad SmartStage.
Digit b bit 0: D.C voltage too low.
Digit b bit 1: 80 W output power exceeded. Controller state values:
0A: NOT REFERENCE from reset.
0B: NOT REFERENCE from HOMING mode.
0C: NOT REFERENCE from CONFIGURATION mode.
0D: NOT REFERENCE from DISABLE mode.
0E: NOT REFERENCE from READY mode.
0F: NOT REFERENCE from MOVING mode.
10: NOT REFERENCE from Smartstage error.
14: CONFIGURATION.
1E: HOMING.
28: MOVING.
32: READY from HOMING mode.
33: READY from MOVING mode.
34: READY from DISABLE mode.
3C: DISABLE from READY mode.
3D: DISABLE from MOVING mode.