09.95
260*
Active:
The multgain factor is used to match the controlled system to the K
NC MD 252*. The multgain is a pure multiplier for the specified K
for precision digital tacho-generator matching in view of the very fine adjustment
capabilities.
Following the correct entry or matching of the multgain, the K
axis must correspond precisely to the specified value.
Note:
Matching of the actual K
different input values would be obtained for the various axes despite identical gain in the
position control loop.
Where U
Multgain = U
If problems of precision or restrictions caused by input limits occur, the factors between MD
256* and 260* can be reduced or increased. See Section entitled "Axis (Analog) and Spindle
Installation". See MD 141 for digital drive.
264*
The specified setpoint speed is monitored; if it is too high (control loop and drive errors), alarm
156* is triggered.
The specified value must be greater than the highest maximum setpoint speed specified in NC
MD 268*.
Recommended value
Approx. 20 % higher than the value in NC MD 268*
See also Section entitled "Axis (Analog) and Spindle Installation".
_______
1)
Up to SW 2
2)
As from SW 3
3)
As from SW 4
©
Siemens AG 1992 All Rights Reserved
SINUMERIK 840C (IA)
More user manuals on
Scaling factor maximum speed setpoint
Default value
Lower input limit
1)
8 000
2)
10 000
3)
9 000
for all channels of mode group in stop
factor via NC MD 252* (K
V
is the speed setpoint voltage at maximum motor speed
max
[mV]
max
Threshold value for drive errors
Default value
Lower input limit
1)
9 600
2)
12 000
ManualsBase.com
6 NC Machine Data (NC MD), NC Setting Data (NC SD)
Upper input limit
1
99 999 999
0
20 000
1
20 000
V
factor) is not to be recommended, as
V
Upper input limit
+0
15 000
0
20 000
6FC5197- AA50
6.4 Axis-specific MD 1 (axial data 1)
Active for all
channels of
mode groups
in STOP
Units
0.01 % of
max. setpoint
factor specified in
V
factor, and should be used
V
factor produced for the relevant
Active on
NC Stop
Units
VELO
0.01% of max.
motor speed
6–47