Technical Data; Input - Siemens SITOP PSU2600 3ph Manual

Table of Contents

Advertisement

Technical data

Note
Technical data apply for a rated input voltage, rated load and 25 °C ambient temperature if
nothing else is specified.
6.1

Input

Input
Rated voltage U
in rated
Voltage range
Wide-range input
Overvoltage strength
Line failure buffering at I
out rated
Rated line frequency
Line frequency range
Input current at rated input voltage 400 V
Input current at rated input voltage 500 V
Inrush current limiting (25 °C), max.
I²t, max.
Integrated input fuse
Protection in the line feeder cable (IEC 898)
SITOP PSU2600 3ph
Manual, 01.2018, A5E39263454-2-76
, min.
6EP4436-0SB00-0AY0 (24 V/20 A)
3-phase, AC
400 - 500 V
340 - 575 V
Yes
-
15 ms
50 - 60 Hz
47 - 63 Hz
1.2 A
1 A
16 A
0.8 A
s
2
None
required: 3-pole, coupled miniature circuit breaker 6 - 16 A
characteristic C or circuit breaker 3RV2011-1DA10 (setting
3 A) or 3RV2711-1DD10 (UL489-listed, DIVQ)
6
27

Advertisement

Table of Contents
loading