Data Sets Sitop Cnx8600 - Siemens SITOP PSU8600 Manual

Psu8600power supply systems
Hide thumbs Also See for SITOP PSU8600:
Table of Contents

Advertisement

Data
ReloadTime
AutoLogout
HttpAccessEnable
Index 0x0040: Identification values (reading/writing)
Data
Contact
Location
7.6.2.3

Data sets SITOP CNX8600

Index 1: Channel1...4 remote target values (reading/writing)
The saved data of an output are listed in the table below. The data applies to outputs 1 to 4.
Data
Utarget [10mV]
Ilimit [10mA]
Ithreshold (0-100%)
OutputEnable (0/255)
Reset
PSU8600power supply systems
Manual, 04.2016, A5E35883207-7-76
Description
Currently set setpoint of the output voltage.
Response threshold of the output current for an output. When this is exceeded,
the output current is interpreted as having an overload condition and is shut
down with a time delay - or limited.
Prewarning threshold of the configured response threshold for the output cur-
rent in %. An alarm is initiated when the actual output current exceeds this
value. Operation is continued without any restrictions. Prewarning is deactivat-
ed by entering "0 %".
Switch on output Switches the output on or off. A possible automatic shutdown
due to overload or power failure is not taken into account.
Resets the output: Resets the automatic overload shutdown of an output. As-
suming that the output is not switched off elsewhere, then after the reset, it is
switched on again.
Description
Update interval:
0: Off
5: 5 s
10: 10 s
20: 20 s
30: 30 s
60: 60 s
Enable/disable automatic logoff:
0: disable
255. enable
When automatic logoff is activated, the logged on
user ("Guest" or "Admin") is automatically logged
off when the SITOP PSU8600 web server is inac-
tive for 15 minutes.
Disable/enable access only via HTTPS
Description
Name of the contact person. You can change the
name to suit your requirements.
Location designation: Indicates the unique location
of the SITOP PSU8600.
Engineering and remote access
7.6 Cyclic and acyclic data
Data type
Unsigned8
Unsigned8
Unsigned8
Data type
VisibleString(64)
VisibleString(44)
Data type
Unsigned16
Unsigned16
Unsigned8
Unsigned8
Unsigned8
213

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitop cnx8600Sitop buf8600

Table of Contents