Appendix 3 Details Of Remote Buffer Memory - Mitsubishi Electric NZ2GF2BN-60DA4 User Manual

Cc-link ie field network digital-analog converter module
Table of Contents

Advertisement

Appendix 3
This section describes the details of remote buffer memory areas of the D/A converter module.
(1) Mode switch
Set the mode for all channels.
Normal mode
Trigger output mode
Automatical judgment mode
Setting a value other than the above results in the error code (0730H) being stored in Latest error code (RWr0),
Error flag (RXA) turning on, and the ERR. LED lighting up, with Automatical judgment mode (9H) set up.
(a) Enabling the setting
1.
Turn on and off Initial data setting request flag (RY9).
2.
Check that "0920H" is stored in Latest warning code (RWr1).
3.
Turn off and on the power supply.
(b) Default value
The default value is Automatical judgment mode (9H).
(c) Remote buffer memory address
The remote buffer memory address of this area is as follows:
Remote buffer memory name
Mode switch
184
Details of Remote Buffer Memory
Mode
Main D/A converter module
0000H
Setting value
0H
1H
9H
Extension D/A converter module

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2ex2b-60da4

Table of Contents