(7) Analog output HOLD/CLEAR function
The following describes Trigger output request (RY19, RY29) and the analog output HOLD/CLEAR function.
• Even if Trigger output request (RY19, RY29) is turned on while the analog output HOLD/CLEAR function is
being executed, the D/A conversion is not performed. This is the same for the trigger output request
assigned to the extension digital input module as an external signal.
• Even when the operating status of the CPU module is back to RUN, the analog output value is not updated
until the D/A conversion is performed by another Trigger output request (RY19, RY29).
Trigger output request
(RY19, RY29)
after external signal assignment
D/A conversion processing
Analog output value of CH1
(CLEAR setting)
Analog output value of CH2
(HOLD setting)
Trigger output completed flag
(RX19, RX29)
Trigger output completed clear
request (RY1A, RY2A)
Operating status of CPU module
114
Controlled by the D/A converter module
Controlled by the program
ON
ON
OFF
OFF
1st D/A
conversion
Waiting for
Waiting for
trigger input
trigger input
1st D/A
conversion value
1st D/A conversion value
1st D/A
conversion value
ON
OFF
OFF
ON
OFF
OFF
RUN
OFF
During execution of the HOLD/CLEAR function,
a trigger output request is denied.
ON
OFF
OFF
Analog output
2nd D/A
HOLD/CLEAR
conversion
function in execution
Waiting for
trigger input
Offset value
Offset value
1st D/A conversion value
ON
If the CPU module is turned to RUN,
the analog output value is not updated
until next D/A conversion.
RUN
Waiting for
trigger input
2nd D/A
conversion value
2nd D/A
conversion value
OFF
ON
OFF