Mitsubishi Electric NZ2GF2BN-60DA4 User Manual page 131

Cc-link ie field network digital-analog converter module
Table of Contents

Advertisement

(2) External signal assignment function
This function allows remote input or output signals of the main D/A converter module to be assigned to remote
I/O signals of the extension I/O module connected. Signals can be input from the extension I/O module and error
signals can be output to the external at the fixed timing without influence from the sequence scan or link scan.
Target remote I/O signals of external signal assignment
Trigger output request (RY19)
Alert output signal (RX1E)
Error flag (RXA)
Warning flag (RX7)
(a) How the external signal assignment function operates
Ex.
Assigning Alert output signal (RX1E) of a main D/A converter module to RY2A of an extension output
module
Main D/A converter module
Alert output
signal
Alert output signal (RX1E)
Controlled by means of
the external signal assignment
function
RY2A
(extension output module)
lamp (external device)
Assigning a remote input signal of the main D/A converter module to a remote output signal of the extension output module
does not allow the assigned remote output signal to be turned on/off or monitored by program. Turn on/off or monitor the pre-
assigned remote input signal of the main module. (In the above example, turn on/off or monitor RY2A.)
"Trigger output signal assignment"
"Alert output signal assignment"
"Error flag assignment"
"Warning flag assignment"
Extension output module
RX1E
Direction of data flow
The lamp (external device) connected to
the extension output module turns on.
Controlled by the D/A converter module
ON
OFF
ON
OFF
Lights out
Area to be set
RY2A
(external device)
OFF
OFF
Lights up
Lights out
CHAPTER 8 FUNCTIONS
Lamp
129
8