(3) Resetting a check code
The check codes can be reset by either of the following two methods.
• Write a digital value within the setting range, and turn on and off Error clear request flag (RYA).
• Turn on and off Initial data setting request flag (RY9).
(4) When the scaling function is enabled
When Scaling enable/disable setting (address: 010EH, 020EH) is set to Enable (0), the scale-converted digital
value is the target for the check code.
When the scale-converted digital value is out of the setting range, a slight inaccuracy may be contained in the target digital
value for the check code when the check code is stored due to an operational error in the scale conversion.
(5) When the shift function is enabled
When a value is set for CH Shifting set value (RWw6 to RWw9, RWw16 to RWw19), the value with the shifting
set value added is the target for the check code.
(6) Operation example of the check code detection
Ex.
When values are set for a channel with output range of -10 to 10V in the main D/A converter module as
follows:
• "CH Scaling enable/disable setting": "0: Enable"
• "CH Scaling upper limit value": 24000
• "CH Scaling lower limit value": -24000
• "CH Shifting set value (RWw6 to RWw9)": -200
CHAPTER 8 FUNCTIONS
105
8