(c) Precautions for external wiring
To obtain the maximum performance from the functions of the D/A converter module and improve the system
reliability, an external wiring with high durability against noise is required. Precautions for external wiring are as
follows:
• Use separate cables for the AC control circuit and the external output signals of the D/A converter module
to avoid the influence of the AC side surges or induction.
• Do not install cables together with the main circuit lines, high voltage lines, or power cables for equipment
other than the programmable controller. Noise, surges, or induction may affect the system.
• Ground the shielded wires or shielded cables at one point on the programmable controller side. However,
depending on the external noise conditions, it may be better to ground them externally.
(d) External wiring
The following shows the external wiring.
• For voltage output
*1
For the cable, use the 2-core shielded twisted pair cable.
*2
If there is noise or ripples in the external wiring, connect a 0.1 to 0.47F capacitor (25V or higher voltage-resistant
product) to the input terminal of the external device.
• For current output
*3
For the cable, use the 2-core shielded twisted pair cable.
*4
If there is noise or ripples in the external wiring, connect a 0.1 to 0.47F capacitor (25V or higher voltage-resistant
product) to the input terminal of the external device.
66
D/A
conversion
Filter
D/A
conversion
Filter
*1
Motor drive
*2
module and others
1k
V+
to
COM
1M
GND
+24V
24G
FG
*3
Motor drive module
*4
and others
0
I+
to
COM
600
GND
+24V
24G
FG

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2ex2b-60da4

Table of Contents