8.5
Conversion Speed and Conversion Period
Conversion speed is the rate at which the D/A converter module converts and outputs digital values.
The conversion period is the period for D/A conversion in a channel.
The following figure shows the relationship between conversion speed and a conversion period.
The conversion period varies depending on the type of main analog module, the conversion speed, the type of
extension module, and the number of conversion enabled channels.
The following table shows the classification.
Main analog module
Extension module
• Not connected
• Extension I/O
module
Main D/A converter
Extension D/A
module
converter module
Extension A/D
converter module
• Not connected
• Extension I/O
module
Main A/D converter
Extension A/D
module
converter module
Extension D/A
converter module
*1
For an A/D converter module, this column corresponds to the sampling period.
*2
For details, refer to the following:
• CC-Link IE Field Network Analog-Digital Converter Module User's Manual
(1) When an extension module is not connected or an extension I/O module is
connected
The conversion speed is 100s/channel. The conversion period is given by the following:
Conversion period = Conversion speed (100s) Number of conversion enabled channels
Ex.
Assuming that the number of conversion enabled channels is 4
Main D/A converter module
(conversion enabled
channels: CH1 to CH4)
Conversion period = 100s 4 = 400s
88
Conversion
speed
CH1
Processing including
conversion processing
Conversion
processing
of other channels
Conversion period
: Period for conversion processing of one channel
Conversion
speed setting
• 100s
• 400s
• 1ms
100s
400s
1ms
• 100s
• 400s
• 1ms
Conversion period of the main D/A converter module
100μs
100μs
100μs
CH1
CH2
CH3
Conversion
Conversion
Conversion
processing
processing
processing
CH1
Conversion
processing
*1
Conversion period
100s Number of conversion
enabled channels
200s Number of conversion
enabled channels
200s Number of conversion
enabled channels
Conversion speed Number of
conversion enabled channels
200s Number of conversion
enabled channels
500s Number of conversion
enabled channels
1ms Number of conversion
enabled channels
200s Number of conversion
enabled channels
100μs
100μs
CH4
CH1
Conversion
Conversion
Conversion
processing
processing
processing
Reference
Page 88, Section 8.5 (1)
Page 89, Section 8.5 (2)
Page 90, Section 8.5 (3)
*2
Page 90, Section 8.5 (4)
100μs
100μs
100μs
CH2
CH3
CH4
Conversion
Conversion
processing
processing