(2) Initial data setting completed flag
After writing parameter data to the remote buffer memory using the REMTO instruction, turn on Initial data setting
request flag (RY9).
Upon completion of the change of operating conditions, Initial data setting completed flag (RX9) turns on.
For the remote buffer memory items that require Initial data setting request flag (RY9) to be turned on and off to
enable written parameter data, refer to the following:
( Page 37, Section 3.7)
*1
Module power supply
Initial data setting completed flag
(RX9)
Initial data setting request flag
(RY9)
Parameter area
*2
Remote READY (RXB)
*1 Assume that a data link is established simultaneously with turning on of the module power supply.
*2 If Initial data setting request flag (RY9) is turned on and off, check the turning on of Remote READY (RXB) to start the control.
(a) Device number
The device number of this input signal is as follows:
Initial data setting completed flag
170
Controlled by the D/A converter module
Controlled by the program
ON
OFF
OFF
OFF
Reads settings from
the non-volatile memory
(Set value A)
Starts operation
with the set value A
ON
OFF
Signal name
RX9
ON
ON
Setting value change
by user
OFF
Main D/A converter module
OFF
OFF
(Set value B)
Starts operation with the set value B
at this timing
ON
Extension D/A converter module