Mitsubishi Electric NZ2GF2BN-60DA4 User Manual page 88

Cc-link ie field network digital-analog converter module
Table of Contents

Advertisement

4.
Check that "0920H" is stored in Latest warning code (RWr1).
[Online]  [Monitor]  [Device/Buffer Memory Batch]
5.
The D/A converter module starts operating in the set drive mode by turning off and on the module
power supply or performing remote reset.
● For normal mode operation of the D/A converter module connected to a master station that supports the CC-Link IE Field
Network synchronous communication function, set to "0: Normal conversion mode".
● In the MELSEC iQ-R series master station, setting each slave station to Synchronous or Asynchronous allows their
operation (synchronous communication mode or normal mode) to be managed and configured at a time by the master
station. Note, however, that settings for the extension modules have no effect. Their operation follows the settings of the
main module connected.
(2) Drive mode of extension modules
When an extension analog module is connected to a main analog module, the extension analog module operates
in the drive mode corresponding to that of the main analog module.
The following table lists the details.
Main analog module
Main A/D converter module
Main D/A converter module
86
Extension analog module
Extension A/D converter module
Extension D/A converter module
Extension A/D converter module
Extension D/A converter module
Drive mode of main analog module
Normal mode
Trigger conversion mode
Synchronous communication mode
Normal mode
Trigger conversion mode
Synchronous communication mode
Normal mode
Trigger output mode
Synchronous communication mode
Normal mode
Trigger output mode
Synchronous communication mode
Drive mode of extension analog
module
Trigger output mode
Trigger conversion mode