Appendix 2
The following describes the details of buffer memory.
(1) D/A conversion enable/disable setting (Un\G0)
Set whether to enable or disable D/A conversion for each channel.
(a) Enabling the setting
Turn OFF  ON  OFF Operating condition setting request (Y9) to enable the setting.
(b) Default value
All channels are set to D/A conversion disable (1).
(2) CH Digital value (Un\G1 to Un\G8)
This is the area where the digital value in signed 16-bit binary for performing the D/A conversion is written from
the CPU module.
• The setting range is as follows;
Module
Output range setting
0: 4 to 20mA
1: 0 to 20mA
2: 1 to 5V
L60DA4
3: 0 to 5V
4: -10 to 10V
F: User range setting
0: 4 to 20mA
1: 0 to 20mA
2: 1 to 5V
L60DAVL8,
3: 0 to 5V
L60DAIL8
4: -10 to 10V
F: User range setting
*1
When the scaling function is enabled, the settable range and practical range depend on the settings for scaling upper
and lower limit values.
• When the value out of the setting range is written, the D/A conversion is performed with the upper and lower
limit value of the settable range. In addition, a check code is stored in CH Set value check code (Un\G11 to
Un\G18) and the error code (60) is stored in Latest error code (Un\G19), Error flag (XF) turns on, and the
ERR. LED turns on.
190
Details of Buffer Memory Addresses
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5
0
0
0
0
0
b4 to b15 of the L60DA4, and b8 to b15 of
the L60DAVL8 and L60DAIL8 are fixed to 0.
Settable range (practical range)
0 to 20479
(practical range: 0 to 20000)
-20480 to 20479
(practical range: -20000 to 20000)
0 to 8191
(practical range: 0 to 8000)
-16384 to 16383
(practical range: -16000 to 16000)
-8192 to 8191
(practical range: -8000 to 8000)
Common
b4
0
0
0
CH8
CH7
CH6
CH5
0: D/A conversion enable
1: D/A conversion disable
Common
If the scaling function is disabled
A written digital value out of the
settable range is treated as
20480 or more: 20479
-1 or less: 0
20480 or more: 20479
-20481 or less: -20480
8192 or more: 8191
-1 or less: 0
16384 or more: 16383
-16385 or less: -16384
8192 or more: 8191
-8193 or less: -8192
b3
b2
b1
b0
CH4
CH3
CH2
CH1
If the scaling function is
Settable range
-32000 to 32000
*1
enabled