(6) CH Shifting set value
Set the shifting set value that is to be used for the shift function in signed 16-bit binary. The digital value with shift
addition is D/A converted.
For details on the shift function, refer to the following:
• Shift Function ( Page 100, Section 8.10)
(a) Setting range
The setting range is -32768 to 32767.
(b) Enabling the setting
Once a value is set, the shifting set value is valid regardless of turning on and off Initial data setting request flag
(RY9).
(c) Default value
The default value is 0 for all channels.
(d) Device number
The device numbers of this remote register are as follows:
Remote register name
CH Digital operation value
Main D/A converter module
CH1
CH2
CH3
RWw6
RWw7
RWw8
RWw9
Extension D/A converter module
CH4
CH1
CH2
CH3
RWw16
RWw17
RWw18
APPX
A
CH4
RWw19