(5) Setting procedure (D/A converter module)
1.
On the "CC IE Field Configuration" window, select the main D/A converter module from "List of
stations", and set the values as follows:
• When the master station is a simple motion module, set "Station No." to 17 or more.
• In "RX/RY Setting", make an assignment of 32 points.
• In "RWw/RWr Setting", make an assignment of 16 points.
2.
Open the "Parameter Processing of Slave Station" window, and set "Method selection" to
"Parameter write".
"CC IE Field Configuration" window  Select the main D/A converter module from "List of stations"
[CC IE Field Configuration]  [Online]  [Parameter Processing of Slave Station]
3.
In "Station parameter", set "Mode switch" to "9: Automatical judgment mode".
4.
In "Basic module parameter", set "CH D/A conversion enable/disable setting" to "0: Enable".
5.
Click
6.
Check that "0920H" is stored in Latest warning code (RWr1).
[Online]  [Monitor]  [Device/Buffer Memory Batch]
7.
Turn off and on the module power supply or perform remote reset to operate the D/A converter
module in synchronous communication mode.
For the extension D/A converter module, make the settings for each item of "Ext. module 1_Module parameter".
124
button to write the parameters to the D/A converter module.