CHAPTER 6
This chapter describes the installation and wiring of the D/A converter module.
6.1

Station Number Setting

(1) Setting method
Set the station number with the rotary switch on the front of the module. Set the station number in the power-off
state because the set value is enabled at power-on.
• The dial x10 is used to set the hundreds and tens place of a station number.
• The dial x1 is used to set the ones place of a station number.
Ex.
For the station number 115, set the switch as shown below.
(2) Setting range
Set the station number, which can be from 1 to 120. A value other than 1 to 120 causes a communication error,
resulting in the D LINK LED flashing.
● While the module power supply is in an on state, changing the station number setting switch causes a minor error,
resulting in the ERR. LED flashing.
When the station number setting switch is set back to the previous state, the module recovers from the error after five
seconds, resulting in the ERR. LED turning off.
● For the station number setting, avoid duplication with the other station numbers. Number duplication causes a
communication error, which does not allow the D LINK LED to light up.