(15)CH Scaling lower limit value, CH Scaling upper limit value
Set the range of scale conversion for each channel.
For details on the scaling function, refer to the following:
• Scaling Function ( Page 95, Section 8.9)
(a) Setting range
• Setting range: -32000 to 32000
(b) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(c) Default value
The default value is 0 for all channels.
(d) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
Remote buffer memory name
CH Scaling lower limit value
CH Scaling upper limit value
● A channel where a value out of the range above is set causes an error with the error code (090H or 190H) being
stored in Latest error code (RWr0), Error flag (RXA) turning on, and the ERR. LED lighting up.
● By default, 0 is set and so change the setting value when using the scaling function.
● The settings must satisfy the condition: Scaling upper limit value > Scaling lower limit value. A channel that does not
satisfy the condition causes an error with the error code (091H or 191H) being stored in Latest error code (RWr0),
Error flag (RXA) turning on, and the ERR. LED lighting up.
● If Scaling enable/disable setting (address: 010EH, 020EH) is set to Disabled (1), the settings of CH Scaling lower limit
value and CH Scaling upper limit value are ignored.
(16)Extension module identification code
The identification code of a connected extension module is stored.
If the extension D/A converter module is connected, 2211H is stored.
For the identification codes of extension modules other than the extension D/A converter module, refer to the
following:
 Manual including the description of the extension module used
(a) Remote buffer memory address
The remote buffer memory address of this area is as follows:
Remote buffer memory name
Extension module identification code
196
Main D/A converter module
CH1
CH2
CH3
010FH
0111H
0113H
0110H
0112H
0114H
Main D/A converter module
Extension D/A converter module
CH4
CH1
CH2
0115H
020FH
0211H
0116H
0210H
0212H
Extension D/A converter module
0700H
CH3
CH4
0213H
0215H
0214H
0216H