(3) Voltage output characteristics
The following graph shows the voltage output characteristics.
10
5
1
Analog output
0
value (V)
-5
-10
-12
-16384
No.
Output range setting
1)
-10 to 10V
2)
0 to 5V
3)
1 to 5V
*2
User range setting 1
(-10 to 10V)
*1
Set the offset value and gain value in the user range setting within the range satisfying the following two conditions:
• Setting range: -10 to 10V
• ((Gain value) - (Offset value))  4.0V
*2
The extension D/A converter modules does not support User range setting 1.
Use the value within the practical digital input range and practical analog output range. If a value is out of the range, the
maximum resolution and accuracy may not fall within the range of performance specifications. (Do not use the value in the
dotted line region in the above graph.)
3)
-16000
-8000
-288
Digital input value
Offset value
0V
10V
0V
5V
1V
5V
*1
*1
1)
2)
0
8000
12000
16000
12287
Gain value
Digital value
-16000 to 16000
0 to 12000
-12000 to 12000
Practical
analog
output range
16383
Maximum resolution
0.625mV
0.416mV
0.333mV
0.333mV
205
APPX
A