Mitsubishi Electric NZ2GF2BN-60DA4 User Manual page 187

Cc-link ie field network digital-analog converter module
Table of Contents

Advertisement

(2) Trigger output signal assignment
Assign Trigger output request (RY19) of the main D/A converter module to Remote input (RX) of the extension
input module using the external signal assignment function. Turning on the assigned Remote input (RX) from off
allows D/A conversion to be performed through the trigger output function.
(a) Setting range
With the head of Remote input (RX) of the main D/A converter module as a starting point (0000H), set the
number, which is counted from the head, of Remote input (RX) of the extension module.
Ex.
When Trigger output request (RY19) is assigned to Remote input (RX) numbered 8H as counted from the
head (0H) of the extension input module
Remote input (RX) numbered 8H as counted from the head of the extension input module corresponds to
Remote input (RX) numbered 28H as counted from the head of the main D/A converter module.
Thus, set 28H for Trigger output signal assignment (address: 0002H).
(b) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(c) Default value
The default value is No assignment (FFFFH).
(d) Remote buffer memory address
The remote buffer memory address of this area is as follows:
Remote buffer memory name
Trigger output signal assignment
● Setting a value out of the range results in the error code (0170H) being stored in Latest error code (RWr0), Error flag
(RXA) turning on, and the ERR. LED lighting up, with the previously set operation.
● With Trigger output signal assignment (address: 0002H) set to Remote input (RX) of the extension input module, turning
on Trigger output request (RY19) from off does not allow D/A conversion. Turn on Remote input (RX), which is set in
Trigger output signal assignment (address: 0002H), from off.
Main D/A converter module
0H
to
1FH 20H
Main D/A converter module
0002H
Extension input module
0H
to
8H
to
FH
to
28H
to
2FH
Extension D/A converter module