(5) Trigger output completed clear request
The following describes the trigger output completed clear request.
(a) Trigger output completed clear request
The following figure shows the operation where Trigger output completed flag (RX19, RX29) turns off by
turning on Trigger output completed clear request (RY1A, RY2A).
Trigger output request
(RY19, RY29)
D/A conversion processing
Analog output value
Trigger output completed flag
(RX19, RX29)
Trigger output completed
clear request (RY1A, RY2A)
Even when Trigger output completed clear request (RY1A, RY2A) is turned on while Trigger output completed
flag (RX19, RX29) is on, the D/A converter module accepts the trigger output request.
Trigger output request
(RY19, RY29)
D/A conversion processing
Analog output value
Trigger output completed
flag (RX19, RX29)
(b) Method for Trigger output completed clear request
The time required until Trigger output completed flag (RX19, RX29) turns off by Trigger output completed clear
request (RY1A, RY2A) depends on the sequence scan time and the link scan time.
To use Trigger output completed flag (RX19, RX29) as an interlock, turn on Trigger output request (RY19,
RY29) after Trigger output completed flag (RX19, RX29) turns off.
112
Controlled by the D/A converter module
Controlled by the program
ON
OFF
OFF
Waiting for
Waiting for trigger input
trigger input
D/A conversion
0
1st D/A conversion value
ON
OFF
ON
OFF
Controlled by the D/A converter module
ON
OFF
OFF
Waiting for
Waiting for trigger input
trigger input
D/A
conversion
0
1st D/A conversion value
ON
OFF
ON
OFF
Waiting for trigger input
D/A
conversion
2nd D/A conversion value
ON
OFF
ON
OFF
ON
OFF
D/A conversion is performed even while Trigger
conversion completed flag (RX19, RX29) is on.
Waiting for trigger input
D/A
conversion
2nd D/A conversion value
OFF
OFF