Trip Coil Monitor; Circuit Breaker Failure Protection - Siemens SIPROTEC 7SJ61 Manual

Multifunction protection with control
Hide thumbs Also See for SIPROTEC 7SJ61:
Table of Contents

Advertisement

3.2.10

Trip coil monitor

ASDU
Function
Informa-
type
tion
number
1
153
16
1
153
17
1
170
51
1
170
52
1
170
53
1
170
54
1
170
55
3.2.11

Circuit breaker failure protection

ASDU
Function
Informa-
type
tion
number
1
160
85
1
166
103
1
166
104
1
166
151
1
166
152
1
166
153
2
166
156
2
166
157
2
166
180
2
166
181
7SJ61 / 7SJ62 / 7SJ64 Bus mapping
C53000-L2540-A306-2
Name
74TC BLOCKED
74TC ACTIVE
>74TC trip rel.
>74TC brk rel.
74TC OFF
74 ProgFail
FAIL: Trip cir.
Name
50BF TRIP
>BLOCK 50BF
>50BF ext SRC
50BF OFF
50BF BLOCK
50BF ACTIVE
50BF int Pickup
50BF ext Pickup
50BF int TRIP
50BF ext TRIP
Description
74TC Trip circuit supervision is BLOCKED; ON = 1, OFF = 0 6862
74TC Trip circuit supervision is ACTIVE; ON = 1, OFF = 0
>74TC Trip circuit superv.: trip relay; ON = 1, OFF = 0
>74TC Trip circuit superv.: bkr relay; ON = 1, OFF = 0
74TC Trip circuit supervision OFF; ON = 1, OFF = 0
74TC blocked. Bin. input is not set; ON = 1, OFF = 0
74TCFailure Trip Circuit; ON = 1, OFF = 0
Description
50BF TRIP; ON = 1
BLOCK 50BF; ON = 1, OFF = 0
50BF initiated externally; ON = 1, OFF = 0
50BF is switched OFF; ON = 1, OFF = 0
50BF is BLOCKED; ON = 1, OFF = 0
50BF is ACTIVE; ON = 1, OFF = 0
50BF (internal) PICKUP; ON = 1, OFF = 0
50BF (external) PICKUP; ON = 1, OFF = 0
50BF (internal) TRIP; ON = 1, OFF = 0
50BF (external) TRIP; ON = 1, OFF = 0
Point List
Obj. -
Adr.
6863
6852
6853
6861
6864
6865
Obj. -
Adr.
1471
1403
1431
1451
1452
1453
1456
1457
1480
1481
37