Examples How To Connect, Configure And Set Vt Inputs For Most Commonly Used Vt Connections - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
4.2.4.2
Line distance protection REL670 2.2 ANSI
Application manual
132kV
120V
3
3
EQUATION1937 V1 EN
The following setting should be used: VTprim=132 (value in kV) VTsec=120 (value in V)
Examples how to connect, configure and set VT inputs for most commonly
used VT connections
Figure
19
defines the marking of voltage transformer terminals commonly used around
the world.
+
+
V
V
Pri
Sec
a)
ANSI11000175 V1 EN
Figure 19:
Commonly used markings of VT terminals
Where:
a)
is the symbol and terminal marking used in this document. Terminals marked with a square
indicate the primary and secondary winding terminals with the same (positive) polarity
b)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-ground
connected VTs
c)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open delta
connected VTs
d)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-phase
connected VTs
It shall be noted that depending on national standard and utility practices the rated
secondary voltage of a VT has typically one of the following values:
100 V
110 V
115 V
120 V
230 V
a
A
A
(X1)
(H1)
(H1)
N
n
N
(H2)
(X2)
(H2)
b)
Section 4
Analog inputs
da
A
(X1)
(H1)
dn
B
(X2)
(H2)
c)
d)
ANSI11000175_1_en.vsd
(Equation 1)
a
(X1)
b
(X2)
85