Signals From Bus-Coupler - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

Section 15
Control
15.4.3.4
710
For a bus-coupler bay in section 2, the same conditions as above are valid by changing
section 1 to section 2 and vice versa.

Signals from bus-coupler

If the busbar is divided by bus-section disconnectors into bus-sections, the signals BC_12
from the busbar coupler of the other busbar section must be transmitted to the own busbar
coupler if both disconnectors are closed.
Section 1
(WA1)A1
(WA2)B1
(WA7)C
ABC_BC
ANSI04000484 V1 EN
Figure 332:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BC_12_CL
Another bus-coupler connection exists between busbar WA1 and WA2.
VP_BC_12
The switch status of BC_12 is valid.
EXDU_BC
No transmission error from any bus-coupler bay (BC).
These signals from each bus-coupler bay (ABC_BC), except the own bay, are needed:
Signal
BC12CLTR
A bus-coupler connection through the own bus-coupler exists between busbar WA1
and WA2.
VPBC12TR
The switch status of BC_12 is valid.
EXDU_BC
No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed. For
B1B2_DC, corresponding signals from busbar B are used. The same type of module
(A1A2_DC) is used for different busbars, that is, for both bus-section disconnector
A1A2_DC and B1B2_DC.
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BC
en04000484_ansi.vsd
1MRK 506 369-UUS -
A2
B2
C
Line distance protection REL670 2.2 ANSI
Application manual