ABB RELION 670 SERIES Applications Manual page 130

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

Section 6
Wide area measurement system
124
every 3 ms while the PHASORREPORT block is expecting input every 0.9 ms. The
PHASORREPORT filtering window is designed to receive updated input every 0.9 ms
and therefore the application will fail.
Rule 2:
The same SMAI or 3PHSUM block can be connected to more than one
PHASORREPORT block only if all the connected PHASORREPORT blocks have
similar instance number or only if all the connected PHASORREPORT blocks have
similar settings for SvcClass and ReportRate. Figure
PMUREPORT function block demonstrated by PCM600 Parameter Setting Tool (PST).
IEC140000126 V2 EN
Figure 41:
PMUREPORT settings in PCM600 PST
Figure
42
shows an example of correct connection of SMAI and PHASORREPORT
blocks in ACT where two different SMAI blocks are connected to different
PHASORREPORT blocks with different instance numbers. In this example, as the
PHASORREPORT blocks have different instance numbers and different settings for
SvcClass and ReportRate, a separate SMAI block is used for each PHASORREPORT
block.
1MRK 506 369-UUS -
41
shows the settings for
IEC140000126-2-en.vsd
Line distance protection REL670 2.2 ANSI
Application manual