ABB RELION 670 SERIES Applications Manual page 517

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI
Application manual
RCA
IDirPU
ANSI05000135 V3 EN
Figure 263:
Relay characteristic angle given in degree
In a normal transmission network a normal value of RCA is about 65°. The setting range
is -180° to +180°.
polMethod: Defines if the directional polarization is from
Voltage (3V
or V
)
0
2
Current (3I
· ZNpol or 3I
0
both currents and voltage, Dual (dual polarizing, (3V
ZNpol)).
Normally voltage polarizing from the internally calculated residual sum or an external
open delta is used.
Current polarizing is useful when the local source is strong and a high sensitivity is
required. In such cases the polarizing voltage (3V
necessary to use current polarizing or dual polarizing. Multiply the required set current
(primary) with the minimum impedance (ZNpol) and check that the percentage of the
phase-to-ground voltage is definitely higher than 1% (minimum 3V
a verification.
RNPol, XNPol: The zero-sequence source is set in primary ohms as base for the current
polarizing. The polarizing voltage is then achieved as 3I
defined as (ZS
-ZS
)/3, that is the ground return impedance of the source behind the
1
0
V pol = 3V
or V
0
Operation
en 05000135-4- ansi. vsd
·ZNpol where ZNpol is RNpol + jXNpol), or
2
) can be below 1% and it is then
0
Section 9
Current protection
2
+ 3I
· ZNpol) or (V
0
0
2
>VPolMin setting) as
0
· ZNpol. The ZNpol can be
0
+ I
·
2
511