ABB RELION 670 SERIES Applications Manual page 677

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI
Application manual
SUCCL
If the circuit breaker closing command is given and the circuit breaker is closed within the
set time interval tUnsucCl, the SUCCL output is activated after the set time interval
tSuccessful.
SYNCFAIL
The SYNCFAIL output indicates that the auto recloser is inhibited because the
synchrocheck or energizing check condition has not been fulfilled within the set time
interval, tSync. Also ABORTED output will be activated.
UNSUCCL
Indicates unsuccessful reclosing.
WFMASTER
Wait from master is used in high priority units to hold back auto reclosing of the low
priority unit during sequential auto reclosing. Refer to the recommendation for multi-
breaker arrangements in Figure 313.
Connection and setting examples
Figure
311
is showing an example of how to connect the auto recloser when used for three-
pole auto reclosing and Figure
recloser when used for single-pole, two-pole or three-pole auto reclosing.
312
is showing an example of how to connect the auto
Section 15
Control
671