Setting Of Voltage Channels; Example; Examples How To Connect, Configure And Set Vt Inputs For Most Commonly Used Vt Connections - ABB RELION 670 Series Applications Manual

Transformer protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 4
Analog inputs
CTs involved in the protection scheme. The rated CT primary current value is set as parameter
CTPrim under the IED TRM settings.
For all other protection applications (e.g. generator, shunt reactor, shunt capacitor and
transformer protection) it is typically desirable to set
current of the protected object. However this is only recommended to do if the rated current
of the protected object is within the range of 40% to 120% of the selected CT rated primary
current. If for any reason (e.g. high maximum short circuit current) the rated current of the
protected object is less than 40% of the rated CT primary current, it is strongly recommended
to set the parameter
among all CTs involved in the protection scheme and installed on the same voltage level. This
will effectively make the protection scheme less sensitive; however, such measures are
necessary in order to avoid possible problems with loss of the measurement accuracy in the
IED.
Regardless of the applied relationship between the
current, the corresponding minimum pickup of the function on the CT secondary side must
always be verified. It is strongly recommended that the minimum pickup of any instantaneous
protection function (e.g. differential, restricted earth fault, distance, instantaneous
overcurrent, etc.) shall under no circumstances be less than 4% of the used IED CT input rating
(i.e. 1A or 5A). This corresponds to 40mA secondary for IED 1A rated inputs and to 200mA
secondary for IED 5A rated inputs used by the function. This shall be individually verified for all
current inputs involved in the protection scheme.
Note that exceptions from the above 4% rule may be acceptable for very special applications
(e.g. when Multipurpose filter SMAIHPAC is involved in the protection scheme).
4.2.4

Setting of voltage channels

As the IED uses primary system quantities the main VT ratios must be known to the IED. This is
done by setting the two parameters
phase value can be used even if each channel is connected to a phase-to-earth voltage from
the VT.
4.2.4.1

Example

Consider a VT with the following data:
132
kV
3
EQUATION2016 V1 EN-US
The following setting should be used:
4.2.4.2
Examples how to connect, configure and set VT inputs for most
commonly used VT connections
Figure
21
world.
80
IBase in the IED to be equal to the largest rated CT primary current
110
V
3
defines the marking of voltage transformer terminals commonly used around the
IBase parameter equal to the rated
IBase parameter and the rated CT primary
VTsec and VTprim for each voltage channel. The phase-to-
VTprim=132 (value in kV) VTsec=110 (value in V)
1MRK 504 152-UEN B
SEMOD55055-44 v3
SEMOD55055-47 v2
(Equation 1)
SEMOD55055-60 v5
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret670

Table of Contents