ABB RELION 670 SERIES Applications Manual page 341

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI
Application manual
LdAngle
LdAngle
RLdRev
ANSI05000196 V1 EN
Figure 160:
Characteristic of load encroachment function
The influence of load encroachment function on the operation characteristic is dependent
on the chosen operation mode of the FRPSPDIS (21) function. When output signal
PHSELZis selected, the characteristic for the FRPSPDIS (21) (and also zone
measurement depending on settings) can be reduced by the load encroachment
characteristic (as shown in figure 161).
X
RLdFwd
LdAngle
LdAngle
en05000196_ansi.vsd
Section 8
Impedance protection
R
335