Short Line Application - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
8.9.2.4
Line distance protection REL670 2.2 ANSI
Application manual
loaded medium long lines. For short lines, the major concern is to get sufficient fault
resistance coverage and load encroachment is not a major problem. So, for short lines, the
load encroachment function could preferably be switched off. See section
impedance limitation, without load encroachment
The settings of the parameters for load encroachment are done in (21), FRPSPDIS (21)
function.
X
Zm
Load impedance area in
ANSI05000495 V2 EN
Figure 151:
Load encroachment phenomena and shaped load encroachment
characteristic defined in Phase selection and load encroachment
function (FRPSPDIS, 21)

Short line application

Transmission line lengths for protection application purposes are classified as short,
medium and long . The definition of short, medium and long lines is found in IEEE Std
C37.113-1999. ). The length classification is defined by the ratio of the source impedance
at the protected line's terminal to the protected line's impedance (SIR). SIR's of about 4
or greater generally define a short line. Medium lines are those with SIR's greater than 0.5
and less than 4
In short line applications, the major concern is to get sufficient fault resistance coverage.
Load encroachment is not so common. The line length that can be recognized as a short
line is not a fixed length; it depends on system parameters such as voltage and source
impedance, see table 19.
Table 26:
Typical length of short and very short line
Line category
Vn
110 kV
Very short line
0.75 -3.5mile
Short line
4-7 miles
forward direction
LdAngle
R
LdAngle
Vn
500 kV
3-15 miles
15-30 miles
Section 8
Impedance protection
"Load
function".
Zm
ZL
LdAngle
LdAngle
RLdFwd
RldRev
ANSI05000495_2_en.vsd
R
315