Redundant Communication - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

Section 20
Ethernet-based communication
20.2
20.2.1
856
IEC61850 Ed2 IEDs and not editable for IEC61850 Ed1 IEDs because in
IEC61850 Ed1 only one access point can be modelled in SCL.
The IP address can be set in IP address. ECT validates the value, the access points have
to be on separate subnetworks.
The subnetwork mask can be set in Subnet mask. This field will be updated to the SCL
model based on the Subnetwork selection.
To select which communication protocols can be run on the respective access points,
check or uncheck the check box for the relevant protocol. The protocols are not activated/
deactivated in ECT, only filtered for the specific access point. For information on how to
activate the individual communication protocols, see the communication protocol
chapters.
To increase security it is recommended to uncheck protocols that are not
used on the access point.
The default gateway can be selected by entering the IP address in Default gateway. The
default gateway is the router that is used to communicate with the devices in the other
subnetwork. By default this is set to 0.0.0.0 which means that no default gateway is
selected. ECT validates the entered value, but the default gateway has to be in the same
subnetwork as the access point. The default gateway is the router that is being used as
default, that is when no route has been set up for the destination. If communication with
a device in another subnetwork is needed, a route has to be set up. For more information
on routes, see the Routes chapter in the Technical manual and the Application manual.
DHCP can be activated for the front port from the LHMI in Main menu/Configuration/
Communication/Ethernet configuration/Front port/DHCP:1

Redundant communication

Identification
Function description
IEC 62439-3 Parallel redundancy
protocol
IEC 62439-3 High-availability seamless
redundancy
Access point diagnostic for redundant
Ethernet ports
IEC 61850
IEC 60617
identification
identification
PRP
-
HSR
-
RCHLCCH
-
Line distance protection REL670 2.2 ANSI
1MRK 506 369-UUS -
ANSI/IEEE C37.2
device number
-
-
-
Application manual