protection trip or from breaker failure protection. When the circuit breaker open position
is set to start the auto recloser, then manual opening must also be connected here. The
inhibit is often a combination of signals from external IEDs via the I/O and internal
functions. An OR-gate is then used for the combination.
MODEINT
The auto reclosing mode is selected with the ARMode setting. As an alternative to the
setting, the mode can be selected by connecting an integer, for example from function
block B16I, to the MODEINT input. The six possible modes are described in table 6 with
their corresponding MODEINT integer value. When a valid integer is connected to the
input MODEINT the selected ARMode setting will be invalid and the MODEINT input
value will be used instead. The selected mode is reported as an integer on the MODE
output.
ON and OFF
These inputs can be connected to binary inputs or to a communication interface block for
external control.
PLCLOST
This is intended for line protection permissive signal channel lost (fail) for example, PLC=
Power Line Carrier failure. It can be connected, when it is required to prolong the auto
reclosing dead time when communication is not working, that is, one line end might trip
with a zone2 delay. If this is used the auto recloser must also be started from zone2 time
delayed trip.
RESET
Used to reset the auto recloser to start conditions. Possible hold by thermal overload
protection will be reset. Circuit breaker position will be checked and time settings will be
restarted with their set times.
RSTCOUNT
There is a counter for each type of auto reclosing and one for the total number of circuit
breaker close commands issued. All counters are reset with the RSTCOUNT input or by
an IEC 61850 command.
SKIPHS
The high-speed auto reclosing sequence can be skipped and be replaced by normal auto
reclosing sequence by activating SKIPHS input before the STARTHS high-speed start
input is activated. The replacement is done for the 1st shot.
Section 15
Control
667