ABB RELION 670 SERIES Applications Manual page 256

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

Section 8
Impedance protection
250
X
ANSI05000722 V1 EN
Figure 122:
Setting angles for discrimination of forward and reverse fault in
Directional impedance quadrilateral function ZDRDIR (21D)
The reverse directional characteristic is equal to the forward characteristic rotated by 180
degrees.
The polarizing voltage is available as long as the positive sequence voltage exceeds 5% of
the set base voltage VBase. So the directional element can use it for all unsymmetrical
faults including close-in faults.
For close-in three-phase faults, the V1
sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is restored.
After 100 ms the following occurs:
If the current is still above the set value of the minimum operating current (between
10 and 30% of the set IED rated current IBase), the condition seals in.
If the fault has caused tripping, the trip endures.
If the fault was detected in the reverse direction, the measuring element in the
reverse direction remains in operation.
If the current decreases below the minimum operating value, the memory resets until
the positive sequence voltage exceeds 10% of its rated value.
AngNegRes
AngDir
R
en05000722_ansi.vsd
memory voltage, based on the same positive
AM
1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI