Example On How To Connect A Phase-To-Phase Connected Vt To The Ied - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

Section 4
Analog inputs
4.2.4.4
88
3)
are three connections made in Signal Matrix Tool (SMT), which connect these three voltage
inputs to first three input channels of the preprocessing function block 5). Depending on the
type of functions which need this voltage information, more then one preprocessing block might
be connected in parallel to these three VT inputs.
4)
shows that in this example the fourth (that is, residual) input channel of the preprocessing block
is not connected in SMT tool. Thus the preprocessing block will automatically calculate 3Vo
inside by vectorial sum from the three phase to ground voltages connected to the first three
input channels of the same preprocessing block. Alternatively, the fourth input channel can be
connected to open delta VT input, as shown in Figure 23.
5)
is a Preprocessing block that has the task to digitally filter the connected analog inputs and
calculate:
fundamental frequency phasors for all input channels
harmonic content for all input channels
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for sequence
quantities)
These calculated values are then available for all built-in protection and control functions within
the IED, which are connected to this preprocessing function block in the configuration tool. For
this application most of the preprocessing settings can be left to the default values. However the
following settings shall be set as shown here:
VBase=66 kV (that is, rated Ph-Ph voltage)
If frequency tracking and compensation is required (this feature is typically required only for
IEDs installed in the generating stations) then the setting parameters
set accordingly.

Example on how to connect a phase-to-phase connected VT to the IED

Figure
22
gives an example how to connect a phase-to-phase connected VT to the IED. It
gives an overview of the required actions by the user in order to make this measurement
available to the built-in protection and control functions within the IED. It shall be noted
that this VT connection is only used on lower voltage levels (that is, rated primary voltage
below 40 kV).
1MRK 506 369-UUS -
DFTReference shall be
Line distance protection REL670 2.2 ANSI