308
2
V
=
Zload
min
S
EQUATION1753-ANSI V1 EN
Where:
V
is the minimum phase-to-phase voltage in kV
S
is the maximum apparent power in MVA.
The load angle LdAngle can be derived according to equation 229:
æ
ö
P
max
=
LdAngle a
cos
ç
÷
è
S
max
ø
EQUATION1623-ANSI V1 EN
where:
Pmax
is the maximal active power transfer during emergency conditions and
Smax
is the maximal apparent power transfer during emergency conditions.
The RLd can be calculated according to equation 230:
=
×
RLd
ZLoad
cos(
LdAngle
)
EQUATION1624-ANSI V1 EN
The setting of RLd and LdAngle is by default set to 80 ohm/phase and 20 degrees. Those
values must be adapted to the specific application.