ABB RELION 670 SERIES Applications Manual page 471

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI
Application manual
2
20
=
=
×
=
ZC
jX
j
0.15
T
200
EQUATION1974 V1 EN
This corresponds to:
j
0.3
=
=
ZC
j
0.15
pu
2.0
EQUATION1975 V2 EN
Set ZC to 0.15 and AnglePhi to 90°.
The warning angle (StartAngle) should be chosen not to cross into normal operating area.
The maximum line power is assumed to be 200 MVA. This corresponds to apparent
impedance:
2
2
U
20
=
=
=
Z
2
ohm
S
200
EQUATION1976 V1 EN
Simplified, the example can be shown as a triangle, see figure 240.
j
0.3
ohm
=
Ð
o
0.15 90
pu
Section 8
Impedance protection
(Equation 439)
(Equation 440)
(Equation 441)
465