Long Transmission Line Application - ABB RELION 670 SERIES Applications Manual

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
8.4.2.6
Line distance protection REL670 2.2 ANSI
Application manual
In short line applications, the major concern is to get sufficient fault resistance coverage.
Load encroachment is not so common. The line length that can be recognized as a short
line is not a fixed length; it depends on system parameters such as voltage and source
impedance, see table 19.
Table 21:
Definition of short and very short line
Line category
Vn
110 kV
Very short line
0.75–3.6 miles
Short line
4–7 miles
The use of load encroachment algorithm in Full-scheme distance protection, mho
characteristic function (ZMHPDIS, 21) improves the possibility to detect high resistive
faults without conflict with the load impedance (see to the right of figure 126).
For very short line applications the underreaching zone 1 can not be used due to that the
voltage drop distribution through out the line will be too low causing risk for
overreaching.
Load encroachment is normally not a problem for short line applications so the load
encroachment function could be switched off meaning LoadEnchMode = Disabled. This
will increase the possibility to detect resistive close-in faults.

Long transmission line application

For long transmission lines the load encroachment will normally be a major concern. It is
well known that it is difficult to achieve high sensitivity for phase-to-ground fault at
remote end of a long line when the line is heavily loaded.
What can be recognized as long lines with respect to the performance of distance
protection is noted in table 22.
Table 22:
Definition of long lines
Line category
Vn
110 kV
Long lines
77 km - 99 km
Very long lines
> 99 km
The possibility to use the binary information from the load encroachment algorithm
improves the possibility to detect high resistive faults at the same time as the security is
improved (risk for unwanted trip due to load encroachment is eliminated). The possibility
to also use the blinder together with the load encroachment algorithm will considerably
Impedance protection
Vn
500 kV
3–15 miles
15–30 miles
Vn
500 kV
350 km - 450 km
> 450 km
Section 8
259