ABB RELION 670 SERIES Applications Manual page 722

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

Section 15
Control
716
Section 1
(WA1)A1
(WA2)B1
(WA7)C
ABC_BC
ABC_LINE
AB_TRAFO
ANSI04000489 V1 EN
Figure 337:
Busbars divided by bus-section circuit breakers
To derive the signals:
Signal
BBTR_OP
No busbar transfer is in progress concerning this bus-section.
VP_BBTR
The switch status of BBTR is valid.
EXDU_12
No transmission error from any bay connected to busbar 1(A) and 2(B).
These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO), and
bus-coupler bay (ABC_BC) are needed:
Signal
1289OPTR
189 or 289 or both are open.
VP1289TR
The switch status of 189 and 289 are valid.
EXDU_12
No transmission error from the bay that contains the above information.
These signals from each bus-coupler bay (ABC_BC) are needed:
Signal
BC12OPTR
No bus-coupler connection through the own bus-coupler between busbar WA1 and
WA2.
VPBC12TR
The switch status of BC_12 is valid.
EXDU_BC
No transmission error from the bay that contains the above information.
These signals from the bus-section circuit breaker bay (A1A2_BS, B1B2_BS) are needed.
Signal
S1S2OPTR
No bus-section coupler connection between bus-sections 1 and 2.
VPS1S2TR
The switch status of bus-section coupler BS is valid.
EXDU_BS
No transmission error from the bay that contains the above information.
Section 2
A1A2_BS
B1B2_BS
ABC_BC
ABC_LINE
AB_TRAFO
en04000489_ansi.vsd
Line distance protection REL670 2.2 ANSI
1MRK 506 369-UUS -
A2
B2
C
Application manual