ABB RELION 670 SERIES Applications Manual page 355

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 506 369-UUS -
Line distance protection REL670 2.2 ANSI
Application manual
Phase-to-ground fault in forward direction
With reference to figure 106, the following equations for the setting calculations can be
obtained.
Index PHS in images and equations reference settings for Phase selection
with load encroachment function FDPSPDIS (21) and index Zm reference
settings for Distance protection function (ZMQPDIS, 21).
Section 8
Impedance protection
349