ABB RELION 670 SERIES Applications Manual page 344

Line distance protection
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

Section 8
Impedance protection
338
Phase selection
"Quadrilateral" zone
IEC05000674 V1 EN
Figure 163:
Operation characteristic for FRPSPDIS (21) in forward direction for
three-phase fault, ohm/phase domain
The result from rotation of the load characteristic at a fault between two phases is
presented in fig 164. Since the load characteristic is based on the same measurement as the
quadrilateral characteristic, it will rotate with the quadrilateral characteristic clockwise by
30 degrees when subject to a pure phase-to-phase fault. At the same time, the
characteristic "shrinks" by 2/√3, from the full RLdFw/RLdRv reach, which is valid at load
or three-phase fault.
X
(ohm/phase)
Distance measuring zone
R
Line distance protection REL670 2.2 ANSI
1MRK 506 369-UUS -
(ohm/phase)
en05000674.vsd
Application manual