Line distance protection REL670 2.2 ANSI
Application manual
The resistive boundary RLdRev for load encroachment characteristic in reverse direction
can be calculated in the same way as RLdFwd, but use maximum importing power that
might occur instead of maximum exporting power and the relevant Vmin voltage for this
condition.

Minimum operate currents

FDPSPDIS (21) has two current setting parameters which blocks the respective phase-to-
ground loop and phase-to-phase loop if the RMS value of the phase current (ILn) and
phase difference current (ILmILn) is below the settable threshold.
The threshold to activate the phase selector for phase-to-ground (IMinPUPG) is set to
securely detect a single phase-to-ground fault at the furthest reach of the phase selection.
It is recommended to set IMinPUPP to double value of IMinPUPG.
The threshold for opening the measuring loop for phase-to-ground fault (3I0Enable_PG)
is set securely detect single line-to-ground fault at remote end on the protected line. It is
recommended to set 3I0BLK_PP to double value of 3I0Enable_PG.
Distance measuring zones, quadrilateral characteristic
ZMQPDIS (21), ZMQAPDIS (21), ZDRDIR (21D)

Identification

Function description
Distance protection zone, quadrilateral
characteristic (zone 1)
Distance protection zone, quadrilateral
characteristic (zone 2-5)
Directional impedance quadrilateral
Impedance protection
IEC 61850
IEC 60617
identification
identification
ZMQPDIS
S00346 V1 EN
ZMQAPDIS
S00346 V1 EN
ZDRDIR
Z<->
IEC09000167 V1 EN
Section 8
ANSI/IEEE C37.2
device number
21
21
21D
223