Section 15
Control
708
Signal
Q1289OPTR
189 or 289 or both are open.
VP1289TR
The switch status of 189 and 289 are valid.
EXDU_12
No transmission error from the bay that contains the above information.
For bus-coupler bay n, these conditions are valid:
1289OPTR (bay 1)
1289OPTR (bay 2)
. . .
. . .
1289OPTR (bay n-1)
VP1289TR (bay 1)
VP1289TR (bay 2)
. . .
. . .
VP1289TR (bay n-1)
EXDU_12 (bay 1)
EXDU_12 (bay 2)
. . .
. . .
EXDU_12 (bay n-1)
ANSI04000481 V1 EN
Figure 329:
Signals from any bays in bus-coupler bay n
If the busbar is divided by bus-section disconnectors into bus-sections, the signals BBTR
are connected in parallel - if both bus-section disconnectors are closed. So for the basic
project-specific logic for BBTR above, add this logic:
Section 1
(WA1)A1
(WA2)B1
(WA7)C
ABC_LINE
ABC_BC
ANSI04000482 V1 EN
Figure 330:
Busbars divided by bus-section disconnectors (circuit breakers)
BBTR_OP
AND
VP_BBTR
AND
EXDU_12
AND
en04000481_ansi.vsd
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
ABC_LINE
Line distance protection REL670 2.2 ANSI
1MRK 506 369-UUS -
A2
B2
C
ABC_BC
AB_TRAFO
en04000482_ansi.vsd